Style 65 Terminal Head Style Thermocouple
Brand: United Electric Controls LtdDoes not ship to OH, United States
Terminal Head Styles 
Type J: The Iron - Constantan "J" curve thermocouple is the most widely used thermocouple; it is versatile and has a relatively low cost. It has a positive Iron wire and a negative Constantan wire and is recommended for reducing atmospheres. The operating range for this alloy combination is from 0° to 750° C (32° to 1380° F) for the largest wire sizes. Smaller size wire should operate in correspondingly lower temperatures. 
Type T: The Copper - Constantan "T" curve thermocouple, with a positive Copper wire and a negative Constantan wire, is recommended for use in mildly oxidizing and reducing atmospheres at temperatures from 0° to 350° C (32° to 660 °F). They are suitable for applications where moisture is present. 
This alloy is recommended for low temperature work since the homogeneity of the component wires can be maintained better than with other base metal wires. Therefore, errors due to inhomogeneity of wires in zones of temperature gradients are greatly reduced. 
Type K: The Chromel™ - Alumel™ "K" curve thermocouple is often used at high temperatures. It has a positive Chromel™ wire and a negative Alumel™ wire and is recommended for use in clean oxidizing atmospheres. The operating range for this alloy is from 0° to 1250° C (32° to 2280° F) for the largest wire sizes. Smaller size wire should operate in correspondingly lower temperatures. 
Type E: The Chromel™ - Constantan "E" curve thermocouple has the highest emf of all standard thermocouples. It has a positive Chromel ™ wire and a negative Constantan wire and is recommended for use in oxidizing, inert or dry reducing atmospheres or for short periods of time in a vacuum. These elements must be protected from sulfurous and marginally oxidizing atmospheres. Type E thermocouples can be used for temperatures from 0° to 900° C (32° to 1650° F). 
Thermocouple Insulation Types 
MI - For higher temperature applications, a Mineral Insulation can be added in the tube. For UE MI thermocouples compressed magnesium oxide is added inside the tube. These are used to measure temperatures of 260° C (500° F) and higher.
Specifications
Approvals & Certifications
- Certificate of Conformance
 
Cable Material
- Armor Cable: Stainless Steel
 - Armor: Teflon Coating
 - PVC Coated Armor Cable
 
Cable Type
- Armored
 
Communication
- HART
 
Conduit Connection
- 1/2" NPT
 - 3/4" NPT
 
Diameter
- Sheath: 0.125 to 0.375" (3.17 to 9.52 mm)
 
Electrical Connectors
- Ceramic Terminal Block
 - Wiring Cable Gland
 
Enclosure, Body Material
- Terminal Head: 316 Stainless Steel
 - Terminal Head: Cast Iron
 - Terminal Head: Cast or Epoxy Coated Aluminum
 - Terminal Head: Nylon
 - Terminal Head: Polypropylene (White or Black)
 
Environmental Protection
- IP66
 - NEMA 4
 - NEMA 4X
 
Input
- 4-20 mA, 2-Wire Transmitter
 
Junction
- Hot Junction: Grounded
 - Hot Junction: Ungrounded
 
Materials of Construction
- Chain, Compression Fitting Material & Ferrule: Stainless Steel
 - Compression Fitting Material & Ferrule: Brass
 - Insulated Conductor & Ferrule: Teflon
 - Leadwire & Jacket: Fiberglass
 - Sheath: 316 Stainless Steel
 - Sheath: Inconel 600
 
NACE & NIST
- NIST Traceable Calibration
 
Name Plate, Tag Material
- Stainless Steel
 
NPT Connection
- 1/2" NPT Male
 - Compression Fitting: 1/4" NPT Male
 - Compression Fitting: 1/8" NPT Male
 
Output
- 4-20 mA, 2-Wire Transmitter, Isolated or Non-Isolated Output
 
Pipe Size
- Nominal Pipe Size for Weld Pad: 1" to 4" (25 to 101.6 mm)
 
Sensor, Probe Type
- E Thermocouple (Single & Dual)
 - J Thermocouple (Single & Dual)
 - K Thermocouple (Single & Dual)
 - Mineral Insulated Thermocouple
 - T Thermocouple (Single & Dual)
 
Temperature Range
- Maximum