The Mite 70 will vent one port to atmosphere while it locks up the pressure in a second line. The tripped position is then held indefinitely until the control signal is restored and a manual reset button is pushed.
The trip point is adjustable from 1 to 100 psi with a simple screw stem. The Mite 70 can also be tripped on demand from a separate remote signal.
Use the Mite 70 to open safety valves in emergency situations, trigger an alarm while locking up a valve or actuate diaphragm motor valves, air cylinders or other pneumatic actuators.
The Mite 73 is similar in design and function to the Mite 70.
A sensitive line monitoring diaphragm and up to four inputs allow even more versatility.
When tripped by either an increasing or decreasing signal, one output is vented to atmosphere while the other is locked up. The Mite 73 can be tripped by remote and is also capable of being reset pneumatically for fully automated control.