Type 900X Miniature I/P, E/P Transducer

Brand: ControlAir

The Type 900X l/P, E/P transducers are a series of compact electronic pressure regulators that convert an electrical signal (current or voltage) to a proportional pneumatic output.

Utilizing internal solid-state feedback circuitry, the Type-9OOX provides precise, stable pressure outputs to final control elements.

Immunity to the effects of vibration or mounting position, high tolerance to impure air, and low air consumption make this unit ideal for use in demanding applications.

The heart of this unique technology is a bimorph piezo actuator that is encapsulated in a protective skin. This protective skin provides defense against the humidity and contaminants often found in process operating environments.
Features
  • Output Signal: 4-20 mA, 0-5 Vdc, 1-9 Vdc, 0-10 Vdc, 1-5 Vdc 
  • Pressure Range: 0 to 100 psig (0 to 6.895 bar, 0 to 689.5 kPa) 
  • Electrical Connections: 1/2" NPT 
  • Process Connection: 1/4" NPT 
  • Temperature Range:
    • Operating: -40° to 70°C (-40° to 158°F) 
    • Storage: -40° to 93°C (-40° to 200°F) 
  • Accuracy: ±0.10% of span 
  • Materials of Construction:
    • Chromate-treated aluminum with epoxy paint 

Specifications

Brand

Air Consumption

  • standard 1.5 scfh (0.04 m³/hour) at Mid Range Typical, High 4.5 scfh (0.13 m³/hour) at Mid Range Typical

Approvals & Certifications

  • ATEX
  • CE
  • CSA
  • FM

Deadband, Approximate

  • 0.02 % of Span

Elastomers

  • Buna-N

Electrical Connectors

  • 1/2” NPT Conduit Fitting with Pigtail
  • DIN 43650
  • Terminal Block

Enclosure Finish

  • Epoxy Paint

Enclosure, Body Material

  • Chromate Treated Aluminum

Environmental Protection

  • IP65
  • NEMA 4X / IP65

Flow Capacity

  • 12.0 scfm (20.0 m³/hour) at psig: 100 (bar: 6.9, kPa: 690)
  • 4.5 scfm (7.6 m³/hour) at psig: 25 (bar: 1.7, kPa: 170) Supply
  • Standard 12.0 scfm (20.0 m³/hour) at psig: 100 (bar: 7.0, kPa: 700) Supply, High 20.00 scfm (34.0 m³/hour) at psig: 130 (bar: 9.0, kPa: 900) Supply
  • standard 4.5 scfm (7.6 m³/hour) at psig: 25 (bar: 1.7, kPa: 170) Supply, High 20.0 scfm (34.0 m³/hour) at psig: 130 (bar: 9.0, kPa: 900) Supply

Hysteresis

  • ± 0.10 % of Span Guaranteed

Input

  • 4-20 mA
  • Vdc: 0-10
  • Vdc: 0-5
  • Vdc: 1-5
  • Vdc: 1-9

Mounting

  • 1.5” Pipe
  • 2” (50.8 mm) Pipe
  • DIN Rail
  • Panel
  • Wall Mounted

NPT Connection

  • 1/4” NPT Female

Operating Temperature

  • -40° to 70° C (-40° to 158° F)

Output Pressure

  • bar: 0 to 6.9
  • kPa: 0 to 689.5
  • psig: 0 to 100

Position Effect

  • No Measurable Effect

RFI/EMI Effect

  • > 0.5 % of Span Change in Output Pressure Per EN 61000-4-3: 1998, Amendment 1, Performance Criterion A

Signal Impedance

  • 10 Kilohms

Storage Temperature

  • -40° to 93° C (-40° to 200° F)

Supply Pressure

  • For Output Range psig: 0 to 15: psig: 25 to 65 (bar: 1.7 to 4.5, kPa: 173 to 448)
  • For Output Range psig: 0 to 30: psig: 40 to 70 (bar: 2.8 to 4.8, kPa: 276 to 482)
  • For Output Range psig: 0 to 60: psig: 70 to 80 (bar: 4.8 to 5.5, kPa: 483 to 551)
  • For Output Range psig: 1 to 17: psig: 22 to 100 (bar: 1.5 to 6.9, kPa: 152 to 689)
  • For Output Range psig: 2 to 100: psig: 105 to 130 (bar: 7.2 to 9.0, kPa: 724 to 896)
  • For Output Range psig: 2 to 60: psig: 65 to 130 (bar: 4.5 to 9.0, kPa 449 to 896)
  • For Output Range psig: 3 to 15: psig: 20 to 100 (bar: 1.4 to 6.9, kPa: 138 to 689)
  • For Output Range psig: 3 to 27: psig: 32 to 100 (bar: 2.2 to 6.9, kPa: 221 to 689)
  • For Output Range psig: 6 to 30: psig: 35 to 100 (bar: 2.4 to 6.9, kPa: 242 to 689)

Supply Pressure Effect

  • No Measurable Effect

Supply Voltage

  • 7-30 Vdc (Less than 3 mA)

Temperature Effect

  • ± 0.07 %/°C (0.045 %/°F) of Span

Trim Material

  • Brass
  • Stainless Steel
  • Zinc-Plated Steel

Vibration Effect

  • < 1 % of Span Under the Following Conditions: 5 to 15 Hz at 0.8” Constant Displacement 15 to 500 Hz at 10 G's

Documentation

show more