3280 2/2-Way Proportional Valve
Brand: Burkert Fluid Control Systems
                Does not ship to OH, United States
            
    
The direct-acting proportional valve of Type 3280 is used for dosing of liquids and gases in closed or open control loops.
The valve features a linear stepper motor as actuator. The integrated electronics simplify the process integration; additional actuation modules are not necessary.
The motor’s power consumption to hold a specific opening position of the valve is zero. This key feature can reduce the energy consumption of a plant dramatically and thus make it more efficient.
Type 3280 is available as standard ON/OFF or proportional valve, as version with integrated positioner and as version with integrated process controller.
                            Specifications
Ambient Temperature Range
- -10° to 60° C (14° to 140° F)
 
Applications
- Flow
 
Approvals & Certifications
- cULus Listed
 - UR
 
BSP Connection
- G 1/2" Female
 - G 1/4" Female
 - G 3/8" Female
 
Communication
- FOUNDATION Fieldbus
 
Consumption
- Power (DN 2-6): 8 W, Max.
 - Power (DN 8, 10): 12 W, Max.
 - Power: < 1 W (Holding Position)
 
Duty Cycle
- 100 % Duty Cycle - Depending on Fluid & Ambient Temperature
 
Electrical Connectors
- M12 Plug (A-Coded, 8-Pin)
 - Process Controller: M12 Socket (A-Coded, 5-Pin)
 
Enclosure, Body Material
- Fluid: Brass
 - Fluid: Stainless Steel
 - Polycarbonate (PC)
 - Polyphenylene Sulfide (PPS)
 
Environmental Protection
- IP54
 
Frequency
- Extension Sensor Input (Process Controller Digital): 5 to 2,000 Hz
 
Hysteresis
- < 5 %
 
Indication
- Status Display: LED
 
Input
- Positioner Analog, Process Controller Analog (Setpoint): 0-20 mA
 - Proportional Valve (Setpoint): 800 Hz (PWM)
 - Proportional Valve, Positioner Analog, Process Controller Analog (Setpoint): 0-10 V
 - Proportional Valve, Positioner Analog, Process Controller Analog (Setpoint): 4-20 mA
 - Standard ON/OFF (Setpoint): 10-30 V (Log 1, Valve Open)
 - Standard ON/OFF, Positioner Analog, Process Controller Analog (Setpoint): 0-5 V (Log 0, Valve Closed)
 
Input Impedance
- Analog Input (Proportional Valve, Positioner Analog, Process Controller): 60 ohms (Current)
 - Analog Input (Standard ON/OFF, Proportional Valve, Positioner Analog, Process Controller): 22 kΩ (Voltage)
 
Interface Connection
- CAN
 
Media
- Liquids
 - Neutral Gas
 
Mounting Position
- Preferably with Actuator Upright
 
NPT Connection
- 1/2" NPT Female
 - 1/4" NPT Female
 - 3/8" NPT Female
 
O-Ring Material
- FKM
 - NBR
 
Orifice Size
- 0.07" to 0.39" (2 to 10 mm)
 
Output
- Digital Current Limit (Standard ON/OFF, Proportional Valve): 100 mA - Max.
 - Positioner Analog, Process Controller Analog: 0-20 / 4-20 mA - (560 ohms, Max.)
 - Positioner Analog, Process Controller Analog: 0-5 / 0-10 V - (10 mA - Max.)
 
Power Supply
- 24 Vdc ± 10 %, Max.
 
Pressure Range
- psi: 0 to 319 (kPa: 0 to 2,200, bar: 0 to 22)
 
Process Temperature
- Fluid: 0° to 70° C (32° to 158° F)
 
Ratio
- Span - 1:100
 
Repeatability
- < 1 % of Full Scale
 
Response Time
- Closure Time: 2.5 seconds (0 to 100 % Stroke)
 
Seat / Seal Material
- Elastometer, Spindle: FKM
 - Elastometer, Spindle: NBR
 - Seal: EPDM
 
Sensitivity
- < 1 % of Full Scale
 
Spindle Material
- Stainless Steel
 
Viscosity
- 600 mm²/sec (cSt) - Max.