Universal Analog Inputs 1 (2 and 3 Optional)
- Update rates, IN1 = 20 Hz, IN2 and IN3 = 10 Hz
Thermocouple
- Type J, K, T, N, C (W5), E, Pt 2, D (W3), B, R, S
RTD
- 2- or 3-Wire platinum, 100, 500, or 1KΩ
- JIS or DIN curves, 1.0 or 0.1 indication
Process
- Input resolution ≈ 50,000 bits at Full Scale
- Range selectable: 0-10 Vdc, 0-5 Vdc, 1-5 Vdc, 0-50 mV, 0-20 mA, 4-20 mA
- Voltage input impedance 20KΩ
- Current input impedance 100 Ω
Digital Inputs (4)
- Update rate = 10 Hz
- Contact or dc voltage, 36 Vdc max
- 10KΩ input impedance
Open Collector/Switched dc
- Internal load switching (nominal): Switched dc, 22 to 28 Vdc, limited @ 30 mA
- External load switching Max.: Open collector 42 Vdc @ 0.5 A
Solid-State Relay
- Zero switched, optically coupled, 0.5A @ 24 Vac min., 253 Vac Max.
Electromechanical Relay
- Form C, 2A @ 250 Vac or 30 Vdc max
- Resistive or inductive load
- Without contact suppression
Process Outputs (Optional Retransmit)
- Update rate = 1 Hz
- User-selectable 0-10 Vdc, 0-5 Vdc, 1-5 Vdc @ 1KΩ min., 0-20 mA, 4-20 mA @ 800 Ω Max.
Resolution
- dc ranges = 2.5 mV nominal
- mA ranges = 5 µA nominal
Calibration Accuracy
- dc ranges = ± 15 mV
- mA ranges = ± 30 µA
- Temperature stability 100 ppm/°C
Alarm Outputs
- Output update rate 1 Hz
- Electromechanical relay, Form C, 2A @ 30 Vdc or 240 Vac Max.
Communications
- EIA-232 and EIA-485 serial communications with Modbus RTU protocol
Safety and Agency Approvals
- UL/C-UL 916 listed, File # E185611 Process Control Equipment
- NEMA 4X and IP65
Terminals
- Touch-safe, removable terminal blocks, accepts 12 to 22-gauge wire
Power
- 100-240 Vac, -15 %, +10 %, 50/60 Hz, ± 5 %
- 39 VA Max. power consumption
- Data retention upon power failure via non-volatile memory. Sensor input isolation from input to input to output to communication circuitry is 500 Vac
Operating Environment
- 32 to 149° F (0 to 65° C)
- 0 to 90 % Relative Humidity, Non-Condensing
- Storage temperature: -40 to 158° F (-40 to 70° C)
Accuracy
- Calibration accuracy and sensor conformity: ± 0.1 % of Span ± 1° C @ 77° F ± 5° F (25° C ± 3° C) ambient, and rated line voltage ± 10 % with the following exceptions: Type T: 0.12 % of Span for -328 to -58° F (-200 to -50° C) Types R and S: 0.15 % of Span for 32 to 212° F (0 to 100° C) Type B: 0.24 % of Span for 1598 to 3092° F (870° C to 1700° C)
- Accuracy span: less than or equal to operating ranges, 1000° F (540° C) min.
- Temperature stability: ± 0.1° F/°F (± 0.1° C/°C) rise in ambient for thermocouples
- ± 0.05° F/°F (± 0.05° C/°C) rise in ambient for RTD sensors
Displays
- Process: 5-digit, 7 segment LED, Red
- Control interface display: 4-Row, 20-character high definition LCD Green