MZ20-8905 Cleaning System

Brand: Burkert Fluid Control Systems
Does not ship to VA, United States

The Cleaning Module MZ20 and the Control Module ME24 are fully compatible to type 8905 systems. 

The Cleaning System is designed to clean the fluidic channels and in case the sensor area in the connected sensor cubes using up to two cleaning liquids. The cleaning is proceeded fully automatically. When a cleaning is requested example by a timer within the Control Module, all necessary steps are started. 

All timers and criteria are user defined and this allows optimized adjustment to the cleaning demand. The cleaning parameters might be set via 7” touch display at the 8905 Online-Analysis-System or by a Burkert Communicator. 

Using the automatic cleaning system allows reducing the manual cleaning of the sensors and improve the long term stability of the measurements. The cleaning system operates without maintenance except the change of empty tanks by new filled cleaning solutions.
Features
  • Automatic cleaning for type MSxx sensor cubes
  • Protection against clogging in the system and inside the sensor cubes for long time accurate measurements
  • Two cleaning liquids for specific cleaning procedures
  • Application specific programmable cleaning cycle

Specifications

Approvals & Certifications

  • CE
  • EMC - EN 61000-6-4
  • UL

Connection Material

  • Fluidic: Stainless Steel

Consumption

  • Power: 14 VA

Electrical Connectors

  • Plug Connection

Enclosure, Body Material

  • Polycarbonate (PC Anthracite, UV Stabilized, UL 94 V0)

Environmental Protection

  • IP20
  • IP65

Gland Material

  • Cable: TPE (Black)

Humidity

  • < 95 % Relative Humidity without Condensation

Materials of Construction

  • Base Block: Polyamide (PA 6C, Black)
  • Fluidics: Aluminum
  • Fluidics: Polypropylene (PP)

Media

  • Water without Particles: Drinking Water
  • Water without Particles: Industrial Water

Mounting

  • DIN Rail Mounting According to EN 50022

Nominal Pressure

  • psi: 43.5 (kPa: 300, bar: 3)

Operating Temperature

  • Ambient: 0° to 40° C (32° to 104° F)

Operating Voltages

  • 24 Vdc ± 10 % - through the Back Plane of the System Typical 8095 Via Bus or External Power Supply

Process Temperature

  • 3° to 40° C (37° to 104° F)

Resistance

  • Terminating: 120 ohms

Seat / Seal Material

  • Seal: EPDM

Storage Temperature

  • Ambient: -20° to 70° C (-4° to 158° F)

show more