Air Consumption
- 0.18 cfm (5.09 L/minute) at 20 psi
Air Supply
- psi: 100 (kPa: 689.5, bar: 6.89)
Ambient Temperature Range
- -20° to 70° C (-4° to 158° F)
Environmental Protection
- Explosion-proof: Exmd II BT6, Exmd II C(H²) T6 & Exia II BT6
- IP66
Flow Capacity
- 2.83 cfm (4.80 m³/hour) at 20 psi
Indication
- Dome Indicator
- Flat Indicator
Linearity
- Within ± 1.5 % of Full Scale
Materials of Construction
- Stainless Steel - Pressure Gauge
NPT Connection
- 1/4” NPT Female - Air Piping Connection
Pressure Range
- psi: 3 to 15 (kPa: 20 to 100, bar: 0.2 to 1) - EPR1200
Repeatability
- Within ± 0.5 % of Full Scale
Resistance
- 235 ± 15 ohms - Input Resistance
Sensitivity
- Within 0.5 % of Full Scale