Adjustment Type
- Captive Clamp Screws
- Factory Set (Pre-Set)
- Set Point Adjustment
Ambient Temperature Range
- -40° to 71° C (-40° to 160° F)
Applications
- Chemical & Petrochemical
- Midstream & Downstream Oil & Gas
- Pharmaceutical Plants
- Pulp & Paper Mills
- Steel & Aluminum Mills
- Wastewater Treatment Plants
Approvals & Certifications
- ATEX Directive (94/9/EC) II 1 G EEx ia IIC T6 Ga Tamb: -50° to 60° C (-58° to 140° F)
- CE
- CRN
- CSA C22.2 No. 24 & 213 - File # E43374
- GOST-R 51330.0, 51330.1, 51330.10 & 51330.14
- Low Voltage Directive (LVD) 73/23/EC & 93/68/EEC
- PED: 97/23/EC
- UL (C,US) 508 & 1604, Class I, Div. 2, Grade A, B, C, D, Class II, Div. 2, Group F, G, Class III
Approvals & Certifications
Deadband
- Temperature Deadband: Typically 4 % of Range Under Laboratory Conditions (21.11° C (70° F) Ambient Circulating Bath at Rate of 0.5° F Per Minute Change)
Electrical Connectors
- 7/8” Diameter Knockout
- 7/8” Hole to 1/2” NPT Female Watertight Conduit Fitting
Electrical Contacts
- Normally Closed
- Normally Open
- Switch Contacts Gold Flashed
Electrical Rating
- 0.5 A at 125 Vdc
- 1 A at 48 Vdc
- 11 A at 125/250 Vac Resistive
- 5 A at 28 Vdc
Enclosure, Body Material
- Gasketed Die Cast Aluminum
Environmental Protection
- Intrinsically Safe
- IP66
- NEMA 4X
Materials of Construction
- Bulb & Capillary Switch: 316 Stainless Steel
- Bulb & Capillary Switch: Brass
Name Plate, Tag Material
- Anodized Aluminum
- Stainless Steel, Paper ID Tag & Wire Attachment
Repeatability
- Set Point Repeatability: ± 1 % of Adjustable Range
Set Point - Decreasing
- -84.4° to 337.8° C (-120° to 640° F)
Set Point - Increasing
- -84.4° to 337.8° C (-120° to 640° F)
Shock
- Set Point Repeats after 15 G, 10 millisecond Duration
Storage Temperature
- -54° to 71° C (-65° to 160° F)
Switch Type
- DPDT
- One SPDT Hermetically Sealed Snap-Action Switch
Vibration
- Set Point Repeats after 2.5 G, 5 to 500 Hz