8177 Ultrasonic Level Measuring Device
Brand: Burkert Fluid Control Systems
                Does not ship to OH, United States
            
    
The Type 8177 is a non-contact ultrasonic level measuring device designed for continuous level measurement in open or closed vessels. 
The unit is suitable for liquids, but also for solids, in virtually all industries, particularly in water and waste water management.
Features- For level measurement up to 8 meters
 - 4-20 mA/HART - 2-Wires
 - Suitable for solids
 - ATEX certification
 
Specifications
Adjustment
- > 3 seconds
 
Ambient Temperature Range
- Conformity Specification: -20° to 41° C (-4° to 105.8° F)
 - With Display, Adjustment Elements: -20° to 70° C (-4° to 158° F) (Operation & Storage)
 
Applications
- Continuous Level Measuring for Fluids & Solids
 - Distance Measuring
 - Open Basins
 - Sludge Container
 
Approvals & Certifications
- ATEX: EN 50014, EN 50020, EN 50284
 - CE
 - EEx ia IIC T6
 - EU
 - NAMUR: NE 21, NE 43
 - PTB
 
BSP Connection
- G 2" Male
 
Class
- Protection: Class II
 
Cover Material
- Polycarbonate (PC)
 
Current
- Fault Signal: < 3.6 mA (Adjustable)
 - Fault Signal: 20.5 mA Output Unchanged
 - Fault Signal: 22 mA (Adjustable)
 
Damping Adjustment
- 63 % of the Input Variable: 0 to 999 seconds
 
Deadband
- Dead Zone: 1.3 ft (0.4 m)
 
Display
- LCD in Full Dot Matrix
 
Electrical Connectors
- Cable Glands M20 x 1.5
 
Electrical Rating
- Short Circuit Rating: 131 mA
 
Enclosure, Body Material
- 316L Stainless Steel, 1.4404
 - Polybutylene Terephthalate (PBT)
 
Environmental Protection
- IP66
 - IP67
 
Frequency
- 55 kHz
 
Humidity
- Operation: 75 % RH, max.
 - Storage: 85 % RH, max.
 
Interval Time
- > 2 seconds
 
Load Resistance
- 1,000 ohms
 
Materials of Construction
- Ground Terminal: 316L Stainless Steel 1.4435
 - Ground Terminal: 316Ti Stainless Steel 1.4571
 
Measuring Error
- < 0.2 % or ± 4 mm
 
Measuring Range
- Liquids: 0.4 to 8 m
 - Solids: 0.4 to 3.5 m
 
NPT Connection
- 1/2" NPT Male
 - 2" NPT Male
 
Operating Voltages
- 14-30 Vdc (Ex ia Instrument)
 - 14-36 Vdc
 - Conformity Specification: 30 V
 
Output
- 4-20 mA / HART (2-Wire)
 
Power
- 983 mW
 
Pressure Range
- bar: -0.2 to 2
 - kPa: -20 to 200
 - psi: -2.9 to 29.02
 
Principle of Operation
- Ultrasonic
 
Process Connection Material
- PVDF
 
Process Temperature
- -40° to 80° C (-40° to 176° F)
 
Resolution
- 1 mm, Max.
 - 1.6 µA
 
Ring Material
- Seal Ring: EPDM
 
Seat / Seal Material
- Process Seal: EPDM
 
Temperature Coefficient
- 0.06 % / 10K (Average Temperature Coefficient of the Zero Signal - Temperature Error)
 
Torque
- Torque Mounting Boss: 25 Nm, Max.
 
Vibration
- Vibration Resistance: Mechanical Vibrations with 4 G at 5 to 100 Hz
 
Wetted Materials
- Transducer: PVDF
 
- Continuous Level Measuring for Fluids & Solids
 - Open basins
 - Distance measuring
 - Sludge container