Series 605 Magnehelic® Differential Pressure Indicating Transmitter

Brand: Dwyer Instruments, LLC

The Series 605 Magnehelic® Indicating Transmitter provides for both visual monitoring and electronic control of very low differential pressure.

The Series 605 is ideal for control applications in building HVAC systems where local indication is desired during routine maintenance checks or necessary when trouble shooting the system.

The The easily read dial gauge is complimented by the two-wire, 4 to 20 mA control signal utilizing the time-proven Dwyer® Magnehelic® gauge mechanical design and Series 600 transmitter technology.

The two-wire design with terminal strip on the rear simplifies connection in any 4 to 20 mA control loop powered by a 10 to 35 VDC supply.
Features
  • Easy to read gauge permits viewing from far away
  • Patented design provides quick response to pressure changes means no delay in signaling and alerting to critical situations
  • Durable and rugged housing and high-quality components combined provides longservice life and minimized down-time

6 models matching criteria
Out of Stock
Out of Stock
Out of Stock
Out of Stock
Out of Stock
Out of Stock

Specifications

Accuracy

  • ± 0.5 % of Full Scale (The Effects of Linearity, Hysteresis & Repeatability, are included)

Approvals & Certifications

  • CE

Compensated Temperature

  • 0° to 48.9° C (32° to 120° F)

Consumption

  • DC: 38 mA - Max.

Electrical Connectors

  • Screw Typical Terminal Block

Loop Resistance

  • DC: 0-1250 ohms, Max.

Media

  • Air
  • Non- Combustible & Compatible Gases

Mounting

  • Flat Aluminum Bracket for Flush Mounting

NACE & NIST

  • NIST

NPT Connection

  • 1/8” NPT Female

Output

  • 4-20 mA

Power Requirement

  • 10-350 Vdc (2-Wire)

Pressure Range

  • Inches WC: 0 to 50
  • Pa: 0 to 500

Pressure Type

  • Gauge

Sensor Orientation

  • Diaphragm in Vertical Position

Size

  • Dial: 4” (100 mm)
  • Gauge: 5”

Span & Zero Adjustments

  • Protected Potentiometers

Stability

  • ± 1 % of Full Scale Per Year

Temperature Effect

  • ± 0.025 % of Full Scale/°F (0.045 % of Full Scale/°C)

Temperature Range

  • -6.67° to 48.9° C (20° to 120° F)

  • Monitor pressures in ducts, rooms, or total building pressures
  • Filter monitoring
  • Local indication of clean room pressures with process signal sent to control room

show more