Ambient Temperature Range
- -40° to 71° C (-40° to 160° F), Set Point Typically Shifts less than 1 % of Range for a 28° C (50° F) Ambient Temperature Change
Applications
- Refrigeration (Chiller) & Compressor
Approvals & Certifications
Approvals & Certifications
- ATEX Ex directive (94/9/EC) II 1 G EEx ia IIC T6, Tamb: -50° to 60° C (-58° to 140° F)
- CE
- CSA C22.2, No. 24 File # E42272
- GOST R 51330.0, 51330.1, 51330.10 & 51330.14
- Low Voltage Directive (LVD) 73/23/EC & 93/68/EEC
- PED: 97/23/EC
- UL (C,US) 508
Deadband
- psi: 2 to 4 (kPa: 13.8 to 27.6, bar: 0.1 to 0.3)
Electrical Connectors
- 7/8” Diameter Conduit Hole
Electrical Contacts
- Normally Closed
- Normally Open
Electrical Rating
- 1 A at 125 Vac Resistive
- 15 A at 125/250/277 Vac Resistive
- 15 A at 125/250/480 Vac Resistive
- 5 A at 125/250 Vac Resistive
Enclosure, Body Material
- Gasketed Die Cast Aluminum
Operating Pressure
- psi: -14.7 to 350 (kPa: -101.4 to 2,413, bar: -1 to 24.1)
Process Connection Material
Proof Pressure
- Differential Proof Pressure - psid: 70 (kPa: 482.6, bar: 4.8)
Repeatability
- ± 1 % of Full Scale Range
Set Point - Decreasing
- bar: 0 to 4.8
- kPa: 0 to 482.6
- psi: 0 to 70
Set Point - Increasing
- bar: 0 to 4.8
- kPa: 0 to 482.6
- psi: 0 to 70
Shock
- Set Point Repeats after 15 G, 10 millisecond Duration
Storage Temperature
- -54° to 71° C (-65° to 160° F)
System Pressure
- bar: 24.13
- kPa: 2,413
- psi: 350
Vibration
- Set Point Repeats after 2.5 G, 5 to 500 Hz