Series RHP Humidity/Temperature Transmitter
Brand: Dwyer Instruments, LLCThe Series RHP Temperature and Humidity Transmitter combine the voltage or current humidity transmitter output with a passive temperature thermistor or RTD output.
The polymer capacitance humidity sensor is not affected by condensation, fog, high humidity, or contaminants. The humidity sensors are available with 2%, 3% or 5% accuracies.
Duct mounted transmitters are available with an optional two-line alpha numeric LCD display.
Features- 2%, 3%, or 5% Accuracy Models
 - Optional LCD Display on Duct Mount Models
 - Radiation Shield Option for Outdoor Installation in direct sunlight
 
Specifications
Brand
Accuracy
- RH: ± 2 % at 25° C
 - RH: ± 3 % at 25° C
 - RH: ± 5 % at 25° C
 - RTD, DIN Class B, ± 0.3° C at 0° C (± 0.54° F @ 32° F)
 - Solid State Band Gap: ± 0.3° C at 25° C (± 0.9° F at 77° F)
 - Thermistor: ± 0.2° C at 25° C (± 0.36° F at 77° F)
 
Approvals & Certifications
- CE
 
Compensated Temperature
- -20° to 60° C (-4° to 140° F)
 
Conduit Connection
- 1/2" NPSM
 
Display
- Duct Mount Only Optional 2-Line Alpha Numeric, 8-Characters/Line
 - LCD Display
 
Electrical Connectors
- Removable Screw Terminal Block
 
Enclosure, Body Material
- PBT - Duct Mount
 - Polycarbonate
 
Environmental Protection
- IP66
 - NEMA 4X
 
Humidity
- 0 to 100 % RH
 
Hysteresis
- ± 1 %
 
Loop Resistance
- 4-20 mA
 
Mounting
- Duct Mount
 
NACE & NIST
- NIST Traceable Calibration Certificate
 
Operating Temperature - Sensor
- -28.9° to 60° C (-20° to 140° F) - Switch Selectable
 
Output
- 0-10 V at 5 mA - Max.
 - 0-5 Vdc
 - 4-20 mA
 
Power Requirement
- 10-35 Vdc
 - 15-29 Vac
 - 15-35 Vdc
 
Repeatability
- ± 0.1 %
 
Resolution
- RH: 0.1 %
 - RH: 0.1° C (0.1° F)
 
Response Time
- 15 seconds
 
Sensor / Probe Material
- Capacitance Polymer
 
Sensor / Probe Type
- RH
 - RTD - DIN 385 (100 ohms, 1 kΩ)
 - Thermistor - 10 Kilo (Typical II & III), 3 Kilo, 20 kΩ
 
Storage Temperature
- -40° to 80° C (-40° to 176° F)
 
Temperature Range
- -40° to 60° C (-40° to 140° F)
 
Thermal Drift
- < 1 % RH/Year
 
- Air Economizers
 - Outdoor Temperature and Relative Humidity Reference
 - Pool Room Humidity Monitoring