Price
Request a Quote
Stock
Out of Stock
Does not ship to OH, United States

Specifications

Adjustment Type

  • Captive Clamp Screws
  • Factory Set (Pre-Set)
  • Set Point Adjustment

Ambient Temperature Range

  • -40° to 71° C (-40° to 160° F), Set Point Typically Shifts less than 1 % of Range for a 28° C (50° F) Ambient Temperature Change

Applications

  • Energy Generation Including Pumps
  • Industrial Gas Production
  • Pulp & Paper
  • Turbines & Compressors
  • Water & Wastewater Treatment

Approvals & Certifications

  • ATEX Ex directive (94/9/EC) II 1 G Ex ia IIC T6 Ga Tamb: -50° to 60° C (-58° to 140° F)
  • CE
  • CSA C22.2 No. 14, File # E42272
  • FM Class 3545
  • GOST-R 51330.0, 51330.1, 51330.10 & 51330.14
  • Low Voltage Directive (LVD) 2006/95/EC
  • PED: 97/23/EC
  • UL (C,US) 508

Approvals & Certifications

  • ISO 9001

Deadband

  • psi: 60 to 800 (kPa: 420 to 5,520, bar: 4.2 to 55.2)

Electrical Connectors

  • 7/8” Hole to 1/2” NPT Female Watertight Conduit Fitting
  • One 3/4” NPT
  • Screw Terminal
  • Two 7/8” Diameter Knockouts

Electrical Contacts

  • Gold Contacts, 1 A at 125 Vac Resistive
  • Normally Closed
  • Normally Open

Electrical Rating

  • 1 A at 125 Vac Resistive
  • 10 A at 125 Vdc Resistive, Deadband & Min. Set Point Will Increase
  • 20 A, 125/250/480 Vac Resistive
  • Close Deadband, 5 A at 125/250 Vac Resistive
  • External Manual Reset, High Ambient, 15 A at 125/250/480 Vac Resistive, Temperatures up to 145° C (250° F)
  • Vapor Sealed, Fungus Resistant Case,15 A 125/250 Vac Resistive

Enclosure Finish

  • Epoxy Powder-Coated

Enclosure, Body Material

  • Gasketed Die Cast Aluminum

Environmental Protection

  • Intrinsically Safe
  • IP66
  • NEMA 4X
  • Weathertight

Indication

  • Single Red Status Light, 115 Vac

Mounting

  • Hole
  • Pipe
  • Surface

Name Plate, Tag Material

  • Stainless Steel, Paper ID Tag & Wire Attachment

NPT Connection

  • 1/4” NPT Female

O-Ring Material

  • Buna-N
  • Viton

Overpressure & Static Pressure Limits

  • Over Range Pressure - psi: 6,000 (kPa: 41,369, bar: 413.7)

Piston Material

  • 303 Stainless Steel

Process Connection Material

  • 303 Stainless Steel

Proof Pressure

  • psi: 10,000 (kPa: 68,948, bar: 689.5)

Repeatability

  • Set Point Repeatability: ± 3 % of Full Scale Range

Service

  • Oxygen Service Cleaning, Alcohol Cleaning to Remove Residue from the Process Connection

Set Point - Decreasing

  • bar: 6.9 to 413.7
  • kPa: 689.5 to 41,369
  • psi: 100 to 6,000

Set Point - Increasing

  • bar: 6.9 to 413.7
  • kPa: 689.5 to 41,369
  • psi: 100 to 6,000

Shock

  • Set Point Repeats after 15 G, 10 millisecond Duration

Storage Temperature

  • -54° to 71° C (-65° to 160° F)

Switch Type

  • DPDT Switch, 10 A at 125/250 Vac Resistive, Deadband & Min. Set Point Will Increase
  • Two SPDT Switch, may be separated up to 100 % of Range

Vibration

  • Set Point Repeats after 2.5 G, 5 to 500 Hz
show more